ACWC : 2 HP through 10 HP Portable Air-Cooled Single Stage Water Chillers

Cold Shot Chillers

Generating/Updating Your Configure-to-Order tool...

See product documents

1

The W5 Engineering Advantage

Icon for award

20+ Years in Testing

Icon for users

All Across North America

Icon for trust

Trusted by Industry Leaders

Icon for clock

24-Hour Engineering Replies

Icon for users

Secure Order Processing

Icon for Award

ISO-Level Quality Assurance

Overview
Specifications
Resources

Cold Shot Chillers ACWC-Q Series Portable Air-Cooled Single-Stage Water Chiller (2 to 10 Ton)

The Cold Shot Chillers ACWC-Q Series is a line of “portable” air-cooled single-stage water chillers from 2 through 10 tons (24,000 to 120,000 BTU/hr). It uses Copeland welded hermetic scroll compressors and a stainless steel brazed plate evaporator, with a large copper condensing coil with aluminum fins behind powder coated, louvered protective condenser panels. A stainless steel centrifugal pump and welded, insulated stainless steel reservoir sit in a powder coated steel frame on casters, and the 2-ton ACWC-24-Q runs on single-phase 208/230 V power.

Features

Dependable Copeland welded hermetic scroll compressors

Stainless steel brazed plate evaporators, vacuum brazed with copper

External brass service valves

Large copper condensing coil with aluminum fins

Powder coated, louvered protective condenser panels

Strong stainless steel centrifugal pumps with safety fuses or thermal protection

Oversized magnetic contactors

Powder coated steel frame and welded stainless steel reservoir

At a Glance

Best for: 2 to 10 ton cooling behind louvered panels on a copper condensing coil

Capacity: 24,000 to 120,000 BTU/hr (7.0 to 35.2 kW); 2-ton model is single phase

Pump & tank: 30 to 55 GPM stainless pump, 25 or 41 gal stainless steel tank

Operating range: 42 to 70 °F (6 to 21 °C) process fluid, 40 to 115 °F ambient

Which model do I need?

Specification

ACWC-24-Q

ACWC-36-Q

ACWC-60-Q

ACWC-90-Q

ACWC-120-Q

Capacity (±5% at 50 °F LCWT / 95 °F ambient)

2 ton, 24,000 BTU/hr (7.0 kW)

3 ton, 36,000 BTU/hr (10.6 kW)

5 ton, 60,000 BTU/hr (17.6 kW)

7.5 ton, 90,000 BTU/hr (26.4 kW)

10 ton, 120,000 BTU/hr (35.2 kW)

Dimensions (approx.)

42" L × 32.5" W × 51.5" H (1,067 × 826 × 1,308 mm)

42" L × 32.5" W × 52.5" H (1,067 × 826 × 1,334 mm)

50.5" L × 38.5" W × 57" H (1,283 × 978 × 1,448 mm)

66" L × 45" W × 56" H (1,676 × 1,143 × 1,422 mm)

73.5" L × 39.5" W × 67" H (1,867 × 1,003 × 1,702 mm)

Weight

563 lb (255 kg)

571 lb (259 kg)

650 lb (295 kg)

1,000 lb (454 kg)

1,500 lb (680 kg)

Pump output

30 GPM @ 30 psi (114 L/min @ 2.07 bar)

30 GPM @ 30 psi (114 L/min @ 2.07 bar)

30 GPM @ 30 psi (114 L/min @ 2.07 bar)

55 GPM @ 30 psi (208 L/min @ 2.07 bar)

55 GPM @ 30 psi (208 L/min @ 2.07 bar)

Tank size

25 gal (95 L)

25 gal (95 L)

25 gal (95 L)

41 gal (155 L)

41 gal (155 L)

ACWC-Q Series FAQ

24 to 120 (2 ton, 3 ton, 5 ton, 7.5 ton, 10 ton), rated ±5% at 50 °F (10 °C) leaving chilled water and 95 °F (35 °C) ambient.

42 °F to 70 °F (6 °C to 21 °C) for standard units (20 °F to 70 °F (−7 °C to 21 °C) for low leaving fluid temperature units).

40 °F to 115 °F (4 °C to 46 °C) for standard units (−20 °F to 115 °F (−29 °C to 46 °C) for outdoor units with optional low ambient modifications).

One year parts; five year compressor.